Features

  • Chinese / English LCD (LCD size 240 × 128, Displays graphics or up to 120 Chinese characters)
  • LCD backlight energy saving function
  • Two-wire transmission
  • Permanent data storage up to 2000 records
  • Synthesized voice alarm function (Voice broadcast for notifying staff on duty)
  • Voice guidance function (during operation)
  • Abnormal temperature protection function (System communication module overload)
  • Communication and circuit wire insulation damage detection
  • Lightning and spike protection
  • Repeater module wiring fault protection, repeater module segmented isolation
  • Display of all repeater module status on a single screen
  • Address table / interlocked table LCD display function
  • Weekly automatic testing function, follow-up buzzer function
  • Two-stage delay function, backup power energy saving function
  • Expandability

a. Optional 17" touchscreen backup color display

        *Fire alarm GUI system / Riser diagram touchscreen fire alarm display panel

b. Connect up to 8 system circuit communication modules, up to 2048 addresses

c. Serial alarm relay interface, up to 2000 points

d. Annunciator syncing : Maximum 16 connected units

e. Using the GUI PC, up to 8 addressable control panels can be controlled to establish a large fire alarm monitoring network.

f.  High speed dot matrix micro-printer using regular paper for printing all event information (optional)

g. Optional functions :

        *Three RS-485 ports for connecting to the central monitoring system PC

*Disaster prevention center fire-fighting equipment monitoring panel

◎Two-wire communication link (shielded twisted line)

◎Saves equipment cost and construction time. Takes up an address

◎Complete monitoring and control : functions include monitoring and control of equipment in the site

◎Real-time display of all disaster-prevention equipment and devices

◎Switch to prevent accidental activation of controls


Specifications Table

Item

Specifications

Model number

 YFR-1

Main power

 AC 110V 50/60Hz、AC 220V 50/60Hz

Number of Addresses/Number of Systems

150/1L

256/1L

512/2L

768/3L

1024/4L

1280/5L

1536/6L

1792/7L

2048/8L

 

Backup power supply

 DC24V

Circuit voltage

 Load Power/Indicating Lamp/Zone Telephone: DC24V

 Communication System Power:AC32V

Power consumption

 Main panel monitoring (Max):500mA

 Communication board (per loop) Monitoring (Max):280mA

Transmission mode

 Select/poll

Alarm relay output mode

 Contact output: Serial alarm relay × 13 groups, up to 2000 points

 (40-point standard contact requirement, expandable to 160 points)

Sound output

 Synthesized voice, voice, or alarm (90 dB or higher)

Body material

 Steel plate with powder coating

 

External dimensions

Box type

Wall-mounted

Addresses / Loops

150/1L

256/1L

512/2L

768/3L

1024/4L

1280/5L

1536/6L

1792/7L

2048/8L

Height (mm)

450

870

Width (mm)

480

560

Depth (mm)

160

200

With 17/19-inch touchscreen

Box type

Wall-mounted

Cabinet

Addresses / Loops

150/1L

256/1L

512/2L

768/3L

1024/4L

1280/5L

1536/6L

1792/7L

2048/8L

Height (mm)

870(17") / 900(19")

1500

Width (mm)

560

560

Depth (mm)

200

260